Federal Kabel

CU/PVC-F (NYAF) 0.6/1KV

SPECIFICATION

SNI IEC 60502-1

APPLICATION

Single core insulated conductor without sheath for general purposes. Suitable for fixed protected installation or control gear for rated voltages up to 0.6/1 kV. Installation in surface mounted or embedded conduits or similar closed system.

AVAILABLE COLORS

CONSTRUCTION

1- Conductor : Annealed Bunched Copper Wire
2- Insulation : PVC (Polyvinyl Chloride)

GENERAL CHARACTERISTICS

Test Voltage : 3.5 kV / 5 Min
Max. Operating Temperature : 70°C & 105°C
Flame Retardant : IEC 60332-1
Min. Tensile Strength : 12.75 N/mm²
Dimension and WeightElectrical Properties
Cross Section AreaConductor DiameterThicknessOverall DiameterCable Weight (100m)DC Resistance 20°CCurrent Carrying Capacity at 30°CShort Circuit Current
ConductorInsulation1 Sec
mm²N x MMmmmmKgMax. Ω/kmMin. M.Ω.kmAkA
1.530 x 0.250.803.202.2712.1050240.17
2.550 x 0.250.863.753.437.4146320.29
457 x 0.301.084.705.394.6140420.46
685 x 0.301.005.107.213.0836530.69
1080 x 0.401.206.4011.801.8332721.16
167 x 18 x 0.401.037.9017.581.1523971.84
257 x 28 x 0.401.289.9027.800.73231282.88
357 x 40 x 0.401.3611.2037.710.52201564.03
507 x 57 x 0.401.5113.2053.110.38201955.75
707 x 80 x 0.401.5514.9072.120.27202438.05
957 x 108 x 0.401.6017.2296.630.212029010.93
12012 x 80 x 0.401.7619.52123.690.162034513.80